UPS Runtime Calculator

–minutes of runtime
–power ceiling
–load vs ceiling
–battery age factor
Load on a 600 VA unitTypical runtimeWhat it buys
25% (90 W)~40 mina long outage’s essential box
50% (180 W)~20 minsave files, watch the storm
75% (270 W)~12 minclean shutdown with margin
100% (360 W)~8 minspin down only
Runtime is non-linear - halving the load nearly triples minutes because inverter overhead is fixed. Consumer VA delivers ~60% as watts (600 VA = 360 W): size by watts, and test yearly - a 5-year-old battery can be at half capacity with every LED glowing.
Runtime is load watts against available watt-hours - the conversion EIA's energy units primer walks through - and derating for inverter losses is why the honest figure always lands short of the box math.

Pick your UPS capacity, put in what it actually carries - a router and laptop pull around 80 watts, a desktop with monitors closer to 200 - and set the battery age. The estimate gives minutes of runtime, the power ceiling in watts, and how hard you are loading the unit.

Vendor pages quote half-load runtime on a new battery in lab conditions. This one uses the field model - consumer units carry roughly 0.15 Wh of battery per VA, about 85% deliverable, aging fast after year two - and says plainly that the goal for most setups is 5 to 10 clean minutes to save work and shut down, not to keep computing through the outage.

How to use

  1. Pick the VA rating printed on the UPS; the watt ceiling is about 60% of it.
  2. Enter the real load - add up the devices plugged in, not what you wish you had.
  3. Set battery age honestly; over three years expect a third gone even with no use.
Good to know โ€” UPS runtime is brutally non-linear: halving the load does not double the minutes, it nearly triples them, because the inverter's fixed overhead eats proportionally more at light loads. A typical 600 VA consumer unit with a half-size load runs about 20 minutes; at full rated load the honest figure is under 10. The VA number also hides the real limit - consumer units deliver only about 60% of their VA as usable watts (a 600 VA is a 360-watt machine), so sizing starts by watts, not VA. What a UPS is FOR shapes the verdict: it is a graceful-shutdown battery, not a generator - ten clean minutes beats two hours of brown-power, because the job is saving your files and spinning down the disk.
Quick reference โ€” Test the runtime once a year with a lamp and a stopwatch: batteries age fast after year three, and the printed minutes assume a new battery at 25 degrees C. Replace on the test, not on the calendar - a five-year-old battery can be at half capacity while every LED on the box still glows confident.

Frequently asked questions

How long will a 1000VA UPS run a router and laptop?

At about 80 watts combined, expect roughly 90 minutes from a healthy battery. The same unit at a 500 W desktop load drops to about 13 minutes - load, not the VA badge, sets the clock.

Why does my UPS die in minutes when the box said longer?

The box quotes half-load runtime on a new battery. Batteries lose 20-30% of capacity by year three even unused, and loads creep up as devices accumulate - both shave the same curve.

Should I buy a UPS sized for hours of runtime?

No - past 10-15 minutes each extra hour buys expensive battery banks and lithium conversions. The standard play is a short-run UPS on anything with unsaved work, and a generator or power station for duration.

Do UPS batteries need replacing?

Every 3-5 years regardless of use - they age on the shelf. If the self-test beeps or runtime visibly halves, swap in the same spec; a fresh battery makes an old UPS genuinely new again.

Related tools